Synchronization Unit

LD 74501
Synchronization Unit
Synchronization Unit
Synchronization Unit

Description

Suitable for synchronizing a three-phase synchronization generator with the mains or with a second generator. The unit activates the synchronization switch 745563 via a relay output when the synchronizing conditions are correct (voltage, frequency, phase). The synchronizing conditions are automatically set by the synchronization unit. Voltage adjustment of the generator is carried out via the excitation voltage controller using two relay contacts. The speed of the generator drive (frequency) is adjusted via the control voltage controller and the DC stabilizer using two relay contacts.

Technical data

Voltage adjustment:
permissible voltage difference: 0.1...15.0 %
Relay switch-on time: 20...250 ms

Frequency adjustment:
permissible frequency difference: +/- 0.49 Hz
Relay switch-on time: 0.04...0.5 s
Inherent delay of the synchronization switch: 40...300 ms

LED display for:

  • Enable CB
  • Connection pulse
  • Reply: CB is closed

Buttons to:

  • Scroll display or confirm selection
  • Increase digit
  • Reset and cursor function

Illuminated two-line LC display to indicate:

  • Double voltage and frequency
  • Voltage and frequency difference
  • Phase shift
  • Parameters

- Contact load capacity: 250 V AC, 2 A
- Measured values: V = 50-400 V AC, f = 40-70 Hz

Print page

Contact Us

Technical Service & Support:

Online Service Portal
Do you have any questions or suggestions regarding our devices, products, experiments, equipment sets or about our software? You need spare parts? FORM

Repair Service
You would like to register a repair? FORM

Europe
For European distributors, please visit: European distributors
Worldwide requests
Please contact us per email: sales@ld-didactic.de

 Click here for our contact form and postal address.

Contact Us