Description
Tester PROFITEST 0100S-II
Universal tester with a fully automatic measuring
process controlled by a microprocessor for testing the
protective measures according to DIN VDE 0100 / IEC 60 364-6
Ten test functions are available:
1. Voltage measurement IEC 61 010-1/ EN 61 010-1/ VDE 0411-1
2. Testing fault current circuit breaker IEC 61 557/ EN 61 557/ VDE 0413
3. Earth resistance measurement IEC 61 557/ EN 61 557/ VDE 0413
4. Insulation resistance measurement IEC 61 557/ EN 61 557/ VDE 0413
5. Earth loop resistance measurement IEC 61 557/ EN 61 557/ VDE 0413
6. Phase sequence measurement IEC 61 557/ EN 61 557/ VDE 0413
7. Low resistance measurement IEC 61 557/ EN 61 557/ VDE 0413
8. Frequency measurement DIN VDE 0411
9. Site isolation measurement DIN VDE 0100
10. Phase connection control DIN VDE 0411
Specifications of the device:
- Large clear display, variable inclination
- Simultaneous display of all relevant reference values
of a measurement
- Setting of the desired basic function by means of a
single control wheel, button for "Start" and "(N)"
on the test plug handle
- Compatible with the allachable printer PROFITEST PSI
for instant printout of measured values
- Data transmission to the printer via infra-red interface
- A PC can be connected via the printer PROFITEST PSI
for data storage, protocol production and statistics
(by means of software PC.doc or PC.base-m)
Technical data:
- Voltage measurement: 0 ... 500 V
- Frequency measurement: 15.4 ... 420 Hz
- Testing fault current circuit breaker with nominal
fault current 10, 30, 100, 300, 500 mA:
contact potential 0...70 V
- Testing fault current circuit breaker with increasing
fault current: contact potential 0...50 V
trip current 0.3 I( N) ... 1.3 I( N)
- Earth resistance measurement : 4 ranges,
0.01 Ohm ... 9.99 kOhm
- Insulation resistance measurement: 2 ranges,
0.1 MOhm ... 300 MOhm
- Earth loop resistance measurement: 2 ranges,
0.01 Ohm ... 20.0 Ohm
- Short-circuit current: 6.3 A ... 50 kA
- Internal resistance measurement
of power line: 0.01 Ohm ... 20.0 Ohm
- Low resistance measurement: 0.01 Ohm ... 100 Ohm
- Phase sequence measurement: 15.4 ... 420 Hz,
100 ... 500 V
- Site insulation measurement: 0 ... 999 kOhm
Power supply: 6 batteries of 1,5 V (IEC R6)
The delivery includes:
- 1 measurement adapter for socket with earth contact
- 1 measurement adapter for three-phase systems A3-16
- 1 battery set
- 1 carrying strap
- 1 operating manual